Megohmmeter Test Voltage Guide: Choose the Right Voltage

A megohmmeter (insulation resistance tester) applies a high DC voltage to insulation and measures how much current leaks through it. The test voltage matters. Too low and you may miss weak insulation. Too high and you can stress or damage it. This guide shows how to choose the right test voltage.
Quick answer
Match the test voltage to the rated voltage of the equipment. Typical selections are 250 V or 500 V for low-voltage equipment, 1000 V for equipment rated around 600 V to 1 kV, and 2500 V to 5000 V for medium-voltage equipment. Always follow the equipment manufacturer’s instructions and the standard that applies to your work.
Common test voltages and what they are used for
| Test voltage | Typical use |
|---|---|
| 250 V | Very low-voltage circuits and sensitive electronics |
| 500 V | Low-voltage wiring, small motors and equipment rated up to about 500 V |
| 1000 V | Equipment and cables rated roughly 600 V to 1 kV |
| 2500 V | Medium-voltage motors, cables and transformers |
| 5000 V and above | Higher-voltage motors, generators and switchgear |
These are general guides. Different standards and manufacturers give different tables.
Rule of thumb for motors and rotating machines
A widely used reference is the IEEE 43 guidance for rotating machines, which ties the test voltage to the winding rated voltage:
| Winding rated voltage | Suggested DC test voltage |
|---|---|
| Below 1 kV | 500 V |
| 1 kV to 2.5 kV | 500 V to 1000 V |
| 2.501 kV to 5 kV | 1000 V to 2500 V |
| 5.001 kV to 12 kV | 2500 V to 5000 V |
| Above 12 kV | 5000 V to 10000 V |
Check the current edition of the standard for your case.
How to choose in practice
- Find the rated voltage on the nameplate or datasheet.
- Check the specification. Use the voltage in the manufacturer’s manual or your company procedure if one exists.
- Use the lower option for old or damp insulation. Aged or wet insulation can be damaged by high voltage.
- Use the same voltage every time you test the same asset. Results are only comparable at the same voltage and similar temperature.
Spot test, then trend
A single reading tells you the state today. Trending readings over months and years tells you whether insulation is degrading. Record the test voltage, temperature, humidity and test duration with each result.
Beyond the spot test
- Polarization Index (PI): the ratio of the 10-minute reading to the 1-minute reading. It helps judge insulation condition independent of temperature.
- Dielectric Absorption Ratio (DAR): the ratio of the 60-second reading to the 30-second reading, a quicker alternative.
Safety steps
- De-energize and lock out the equipment before testing.
- Disconnect electronics and surge protectors that could be damaged.
- Keep clear of the leads and equipment while the voltage is applied.
- Discharge the insulation after testing. Capacitive insulation can hold a dangerous charge. Many instruments discharge automatically; wait for it to finish.
- Use leads and an instrument with a rating suitable for the voltage and the installation category.
Next step
Browse our megohmmeters and insulation testers and send us the rated voltage, equipment type and test requirements at info@indomultimeter.net so we can help you shortlist models.